PROGRAMMING CHART
PAR NAME VALUE VALID RANGE (F or _ = factory setting)
P0 RATE UNITS [ ] IMP:
1(T/h),2(LT/h),3(lb/h),4(lb/min) Metric: 1(t/h),2(kg/h),3(kg/min)
P1 RATE [ ] 0.0001 to 99999 (F = 0.000)
P2 LOCAL TOTAL [ ] 1,2,or 5 x .0001,.001,.01,.1,
1,10,100,or 1000
P3 REMOTE TOTAL [ ] 1,2,or 5 x .0001,.001,.01,.1,
1,10,100,or 1000
P4 BELT SPEED [ ] 0.0001 to 99999 (F = 0)
P5 SPEED CONSTANT [ ] 0.0001 to 99999 (F = 0 for variable speed, 100 for constant speed)
P6 BELT LENGTH [ ] 0.0001 to 99999 (F = 0)
P7 TEST REFERENCE [ ] 0.0001 to 99999 (F = 0)
P8 SPAN ADJUST [ ]
0 (off), 1 (% change), 2 (material test)
P9 FACTORING [ ]
0 (off), 1(factor test reference)
P10 LOW TOTAL CUTOFF [ ] 0.0 to 100.0 (F=3.00)
P11 RATE DISPLAY DAMPING [ ]
1 to 999
P12 LOAD DISPLAY DAMPING [ ]
1 to 999
P13 SPEED DISPLAY DAMPING [ ]
1 to 999
P14 RATE OUTPUT DAMPING [ ]
1 to 999
P15 RATE OUTPUT AVERAGE [ ]
0 to 99999
P16 RATE BAR GRAPH ASSIGNMENT [ ]
0 (Rate Output P14), 1 (undamped Rate), 2 (Rate Display, P11)
P17 RATE OUTPUT MIN [ ] 0 to 4095 (F = 631)
P18 RATE OUTPUT MAX [ ] 0 to 4095 (F = 3160)
P19 SPEED ADJUST [ ] 0.0000 to 99999 (F = dynamic speed)
P20 TEST REFERENCE SELECT [ ]
0 (test weight), 1 (ECAL), 2 (test chain)
P21 SENSOR TYPE [ ] 0 (LVDT), 1 (1 load cell),
2 (2 load cells), 4 (4 load cells), 8 (LCPA-08)
P22 ECAL ADJUST [ ]
0 (off), 1(on), 2(adjust), [ ] count
P26 MULTISPAN [ ] 0 to 8 (F = 0)
P30 CALIBRATION DURATION [ ] 0.1 to 99 (whole numbers only for P31 operation, F = 1)
P31 VERIFICATION TOTAL [ ]
0 (off), 1 (HOLD TOTAL), 2 (add to Total)
P32 VERIFICATION TOTAL RES [ ]
0 (same as P2), 1 (P2 x 1/10)
P40 BAUD RATE [ ] 300, 1200, 2400,
9600
P41 DATA TRANSMIT INTERVAL [ ] 0 to 99999 (F = 30)
P42 DATA MESSAGE [ ]
0 (off),1 (Rate),2 (Total),3 (Load),4 (Speed),5 (1,2,3,& 4),9 (System)
P43 SERIAL PRINTER [ ]
0 (off), 1 (on)
P51 RELAY 1 [ ]
0 (off), 1 (Rate), 2 (Load), 3 (Speed), 4 (Fixed)
[ ] (hi) [ ] (lo) [ ] (deadband) in %
P52 RELAY 2 [ ]
0 (off), 1 (Rate), 2 (Load), 3 (Speed), 4 (Fixed)
[ ] (hi) [ ] (lo) [ ] (deadband) in %
P55 100% TEST REFERENCE [ ] 0.0001 to 99999 (F = Rate (P1) / Speed (P4), display only)
P60 SOFTWARE REVISION [ ] 1.00 to 99.99 (display only)
P61 MEMORY TEST [ ] Pass or Fail, (display only)
P63 TOTALIZER CONTACT DUR [ ] 0.025 TO 8.323 seconds (F = 1 until P1 and P3 are set)
P64 ZERO RECORD [ ] (display only)
P65 SPAN RECORD [ ] (display only)
P66 SECURITY LEVEL SELECT [ ]
0(off),1(P#’s),2(P#’s,Total),3(P#’s,Zero,Span),4(P#’s,Total,Zero,Span)
P70 CLOCK/CALENDAR [ ] hrs(0-23),min(0-59),day(1-31),month(1-12),year(00-99)
P71 TIME [ ] HH:MM, (24 hour format, display only)
P72 DATE [ ] YY/MM/DD format (display only)
P77 INITIAL ZERO RESET [ ]
0 (off), 1 (reset)
P80 V/F CONVERTER OUTPUT [ ] 0 to 131,000 counts, (display only)
P81 LOAD CELL A INPUT [ ] 0.00 to 50.00 mV, (display only)
P82 LOAD CELL B INPUT [ ] 0.00 to 50.00 mV, (display only)
P83 LOAD CELL C INPUT [ ] 0.00 to 50.00 mV, (display only)
P84 LOAD CELL D INPUT [ ] 0.00 to 50.00 mV, (display only)
P85 V/F CONVERTER INPUT [ ] -1.00 to 4.00 V, (display only)
P88 INITIAL SPAN RESET [ ]
0 (off), 1 (reset)
P90 MSI NUMBER [ ]
0 (non MSI), 1 to 4 (MSI from tail pulley)
P91 POS B L/C (A+B) [ ] 0 to 131,000 counts
P92 POS B L/C (B) [ ] 0 to 131,000 counts
P93 POS A L/C (B) [ ] 0 to 131,000 counts
P94 POS A L/C (A+B) [ ] 0 to 131,000 counts
P95 LOAD CELL BALANCE [ ] 0 to 131,000 counts
P99 RESET [ ]
0 (off), 1 (Partial), 2 (Master)
P100 PARAMETER LIST [ ] 0 to 99 in groups of 10, (display only)
PL-367 8 – 1