P64 ZERO RECORD (V)
Displays the number of operator initiated Zero calibrations performed since the last Reset (P99) or Initial Zero.
Reset (P77), (F = 0).
P65 SPAN RECORD (V)
Displays the number of operator initiated Span calibrations performed since the last Reset (P99) or Initial Span.
Reset (P88), (F = 0).
P66 SECURITY LEVEL
Defines the level of operator access permitted.
This feature may be utilized to ensure the programming and/or calibration is not inadvertently altered. Access
to all RUN mode displays and the P66 value is permitted at all Security levels. When a security level is
selected, security is not invoked until the RUN mode is entered. From the RUN mode, accessing P66 disables
Security until the RUN mode is entered again.
enter: 0 = full access permitted (F)
1 = parameter values secured
2 = parameter and Total display values secured.
3 = parameter values, Zero and Span calibrations secured.
4 = parameter and Total display values, Zero and Span calibrations secured.
P70 CLOCK/CALENDAR
Defines the current Time and Date, to be maintained by the internal clock.
enter: desired value, (Hours, range = 0 to 23, advances to minutes),
desired value, (Minutes, range = 0 to 59, advances to day),
desired value, (Day, range = 1 to 31, advances to month),
desired value, (Month, range = 1 to 12, advances to year),
desired value, (Year, range = 00 to 99)
P71 TIME (V)
Displays time in twenty-four hour format, (HH:MM).
P72 DATE (V)
Displays date in YY/MM/DD format.
P77 INITIAL ZERO RESET
Performs a Zero Calibration to establish the new Initial Zero count value.
This feature is normally used in response to the [ZERO OUT OF RANGE] message, when the cause of the
deviation is not otherwise correctable. This condition could occur as the result of an intended change in the
Design Parameter values or a mechanical change to the belt or belt scale assembly.
enter: 0 = not required (F)
1 = Initial Zero Reset
PL-367 7 – 12