Milltronics CVCC Manuale delle Istruzioni Pagina 22

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 76
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 21
BIC REPLACEMENT - EXAMPLE
A BIC utilized for communication between an AiRanger DPL and a host device is to be replaced by a BIC-II.
Disconnect the BIC and connect the AiRanger DPL communication cable to the BIC-II \ PORT1. Ensure the
AiRanger DPL is operating at 4800 baud. Refer to the associated instruction manual.
Connect the appropriate BIC-II, RS-232 or RS-422 port to the host device.
Refer to Start Up\Hardware Set Up for BIC-II, board A, switch SW1 and SW2 contact settings.
Revise the computer software or PLC programming to remove any host request messages associated with
the BIC time keeping functions, if applicable.
to
product
PORT
PL-371 6 – 2
Vedere la pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 75 76

Commenti su questo manuale

Nessun commento